Questions and answers on fire alarm transmission

19 answers to the questions we are asked most often about fire alarm monitoring, the FireCom alarm transmission equipment and the receiving station.

If you need information that is not covered here, get in touch.

What is the difference between the alarm transmission equipment and the receiving station?

They are the two ends of the same transmission. The alarm transmission equipment (UTAPiU in Polish; in EN 54-21 terms, alarm transmission and fault warning routing equipment) is the transmitting unit, installed in the protected premises next to the fire alarm control panel. The alarm and fault receiving station (SOAPiU in Polish) is the receiving end, installed at the command post of a Polish State Fire Service headquarters. The whole, i.e. the system connecting the two, is the alarm transmission system (STAPiU). The reference standard for the alarm transmission equipment is EN 54-21 (adopted in Poland as PN-EN 54-21), and for the receiving station CLC/TS 50136-4.

Which buildings must have their fire detection and alarm system connected to the State Fire Service?

Under § 28 of the Regulation of the Polish Minister of the Interior and Administration of 7 June 2010 on fire protection of buildings, the obligation applies, among others, to retail and exhibition buildings above the fire zone floor area thresholds, cultural and entertainment venues (theatres, cinemas, museums, entertainment halls), healthcare facilities (hospitals, sanatoria, hospices), care homes and centres for people with disabilities, large public buildings, transport infrastructure facilities (metro stations, railway and bus stations, airports) and archives designated by the Director General of the Polish State Archives. A full overview is available on the fire alarm monitoring page.

What is the legal basis for connecting a fire detection and alarm system to the fire service?

Three legal acts: the Polish Fire Protection Act of 24 August 1991 (Journal of Laws, Dz.U. 2025 item 188, Article 5), the Regulation of the Minister of the Interior and Administration of 7 June 2010 on fire protection of buildings (Dz.U. 2023 item 822, as amended, § 28 and § 31) and the Regulation of the Minister of the Interior and Administration of 20 June 2007 on the list of products used to ensure public safety (Dz.U. 2007 No. 143 item 1002, as amended), which among other things sets out technical requirements for alarm transmission systems.

How long does the system have to deliver an alarm to the receiving station?

Alarm transmission time is defined by the D and M classes of EN 50136-1-1 (adopted in Poland as PN-EN 50136-1-1). It is measured from the moment the fire alarm control panel passes on the signal to the moment the alarm is made available by the annunciation equipment of the receiving station. The FireCom system operates in classes D4 (under 10 seconds on average) and M4 (20 seconds maximum). The T classes mean something else: the time taken to detect and report loss of a transmission path. The wired path operates in class T5 (90 seconds), the GSM path in class T3 (300 minutes). Overall system classification: D4, M4, T5/T3, A4, S2, I2. Details on the standards and compliance page.

What does availability class A4 mean?

A4 is the highest availability class under EN 50136-1-1. It requires a minimum availability of 98.5% per month and 99.8% per year. The other classes are A0 (no requirements), A1 (75% / 97%), A2 (91% / 99.3%) and A3 (95% / 99.5%). We calculate availability daily using the EN 50136-1-1 method and report it monthly and annually.

Where does FireCom send alarms?

FireCom transmits every alarm simultaneously over two paths, wired IP and cellular GSM (4G/LTE), to the receiving centre of the fire monitoring system operator, Orange Polska S.A. There, the retransmission station decrypts the messages and retransmits the alarm to the receiving station of the relevant State Fire Service headquarters in parallel over two paths, wired and GSM. Once each message has been permanently stored, the retransmission station returns an automatic technical acknowledgement (ACK) to the transmitter. It is the receiving station that receives the alarm and confirms its receipt. The receipt confirmation from the station returns to the control panel in the building as a pulse on the transmitter's PGM1 output; if no confirmation arrives within the set time, output PGM2 is activated.

Does FireCom work without a PSTN telephone line?

Yes. The FireCom system does not use PSTN or ISDN. Transmission is entirely IP-based: the wired path is an Ethernet link in the operator's separate IP MPLS network, and the wireless path is GSM (4G/LTE) via a dedicated APN without Internet access; the two paths are physically different and independent. This matters in practice, because PSTN is being phased out across Europe, which leaves older fire monitoring systems without a transmission medium.

Is the transmission encrypted?

Yes. FireCom uses an encrypted alarm transmission protocol: each protected premises has its own individual encryption key. Event codes are in Contact ID format. Encryption with the per-premises key covers the section from the premises to the receiving centre; beyond that, up to the receiving station, communication is protected by TLS. Both paths operate with no connection to the Internet: the wired path is a dedicated path in a separate IP MPLS network, and the GSM path (4G/LTE) runs in a dedicated APN with SIM cards assigned to the devices.

Which paths does FireCom use to transmit alarms?

FireCom transmits each alarm simultaneously and independently over two physically different paths, in line with the requirements of the Ministry of the Interior and Administration regulation for fire alarm transmission systems. The wired path is a dedicated path in the separate IP MPLS network of Orange Polska, not connected to the Internet, secured at the interface with the premises and continuously monitored for continuity: loss of the path is detected and reported as a fault. The GSM path (4G/LTE) is a dedicated path established in the operator's public network, in a dedicated APN with SIM cards assigned to the devices, without Internet access. The fire monitoring system operator, Orange Polska, holds a radio licence granted on an exclusive basis for this path. Both paths qualify as Type 1 links, either can serve as the primary link, and transmission is bidirectional, so receipt of every alarm message can be confirmed.

What happens if one of the transmission paths fails?

Transmission is initiated over both paths simultaneously, so the alarm gets through on the other path. Loss of one path does not go unnoticed: a fault warning is generated for the service organisation, a path degradation record is created in the availability log, and the interface shows which path the station is operating on. The screens at State Fire Service headquarters are not cluttered with technical events. Under EN 50136-1-1, unavailability only occurs when both paths are lost; loss of one is always signalled and recorded.

How long does the State Fire Service duty officer have to accept an alarm?

In line with CLC/TS 50136-4, alarms enter a queue with pending status, and the duty officer must accept the alarm within a set time. If that time is exceeded, an escalation is generated. The queue is ordered by event priority: fire alarms are handled first.

Is the alarm passed to the State Fire Service command support system (SWD-ST)?

Yes, at headquarters integrated with SWD-ST. The receiving station automatically creates an incident record in the headquarters' SWD-ST; once the alarm has been accepted, the record is completed. Only the receiving station of the given headquarters creates the incident record. Details on the receiving station page.

Are fault warnings also sent to the State Fire Service?

No. Fault warnings from the building's fire detection and alarm system are routed to the operator's fault receiving centre (COSU) run by the fire monitoring system operator, Orange Polska, not to the State Fire Service command post. The fault receiving centre passes them on to service companies. The receiving station, on the other hand, signals its own technical states locally, i.e. faults of the station and of the transmission path, using a yellow lamp with a flashing pattern in accordance with EN 60073.

What are the obligations of the fire monitoring system operator?

In the FireCom system, the fire monitoring system operator is Orange Polska S.A.; F&K Consulting Engineers is the supplier of the solution and a partner of Orange Polska S.A., not the operator. The operator provides round-the-clock operation of the fault receiving station and the monitoring centre, starts repair work within no more than 2 hours of a failure being detected and restores full operation within no more than 24 hours, provides free training for State Fire Service command post staff at least once a year, maintains the receiving station at least once a year, submits an annual statistical report to the State Fire Service commander, and supplies up-to-date lists of monitored premises by 1 January and 1 July each year.

Does FireCom comply with EN 54-21?

Yes. The FireCom alarm transmission equipment holds certificate No. 1922-CPR-2083 confirming conformity with EN 54-21:2006 and EN 54-4, issued by notified body No. 1922 (Dedal), and a declaration of performance (DoP) in accordance with the Construction Products Regulation (CPR, (EU) 305/2011). The system as a whole, including the receiving station, has been designed in line with EN 50136-1-1 and CLC/TS 50136-4.

Does the system have CNBOP-PIB approval?

The FireCom system, together with the receiving station, is currently in the approval process: we are awaiting the Polish National Technical Assessment (KOT) and the CNBOP-PIB certificate of admission (CNBOP-PIB is the Scientific and Research Centre for Fire Protection, National Research Institute, in Józefów, Poland's fire protection approval body). The FireCom alarm transmission equipment holds certificate No. 1922-CPR-2083 confirming conformity with EN 54-21 and EN 54-4. We will confirm the current status of the process on request; please contact us.

How many protected premises can one receiving station handle?

The number of connected premises is unlimited, as is the number of users. The station comes in a 19" RACK enclosure (3U, 4U variant) or in a wall-mounted version. Details on the receiving station page.

How long does the receiving station run without mains power?

30 minutes. The station has a battery-backed power supply that provides 30 minutes of operation without mains power. Loss of AC mains power is signalled by a yellow lamp and reported to the monitoring centre.

How is the FireCom equipment configured?

The FireCom equipment is configured only by an authorised service provider, either locally or remotely over an encrypted channel in the operator's network. The receiving station is configured and updated in the same way, and access to it is divided into four levels in line with CLC/TS 50136-4.