A station installed at the command post of the Polish State Fire Service (PSP) headquarters. It receives fire alarms from FireCom alarm transmission equipment, retransmitted by the receiving centre of the fire monitoring system operator, Orange Polska, and confirms their receipt.
The receiving station (SOAPiU, the Polish acronym for alarm and fault receiving station) is part of the FireCom alarm transmission system. The station is installed at the command post of the district or municipal headquarters of the State Fire Service and receives fire alarms sent by the FireCom alarm transmission equipment installed at the protected premises.
The equipment at the premises sends the alarm simultaneously over two paths, wired IP and cellular GSM 4G/LTE, to the operator's receiving centre. There, the retransmission station, an intermediate device (message switching node), receives both paths, decrypts the message with the per-premises encryption key, automatically sends a technical acknowledgement (ACK) back to the transmitter and retransmits the alarm to the receiving station of the competent State Fire Service headquarters in parallel over two paths, wired and GSM. When the alarm arrives, the event is logged at the station, shown immediately on the touchscreen display, and audible and visual signalling is activated.
Formally, the alarm is received by the receiving station, and it is the station that confirms receipt. The receipt confirmation from the station returns to the fire alarm control panel at the premises, as described below. Separate from this is the automatic technical acknowledgement (ACK) from the retransmission station, required by the transmission protocol.
Fault signals from the premises' fire detection and alarm system are routed to the operator's fault receiving centre, which forwards them to service companies, and are not forwarded to the State Fire Service command post. The station does, however, signal its own technical states locally: faults of the station and of the transmission path.
The retransmission station in the receiving centre gives the transmitter a technical acknowledgement of the message and retransmits the alarm. The alarm is received by the receiving station, and it is the station that sends the receipt confirmation, which travels all the way back to the fire alarm control panel at the premises.
The retransmission station accepts the alarm from both paths and, once the message has been permanently stored, sends an automatic technical acknowledgement (ACK) back to the transmitter; without it, the transmitter repeats the transmission. It then retransmits the alarm to the receiving station of the headquarters responsible for the premises, in parallel over two paths, wired and GSM.
The station sends the receipt confirmation only after the alarm has been permanently stored. The station does not confirm an alarm it cannot present, for example if the display is faulty.
The receipt confirmation from the station returns via the receiving centre to the transmitter: output PGM1 sends a pulse to the control panel (a requirement of EN 54-21, adopted in Poland as PN-EN 54-21). No confirmation within the set time, or loss of communication between the centre and the station, switches output PGM2 to a steady state.
Both confirmations, the automatic technical acknowledgement (ACK) from the retransmission station and the receipt confirmation from the receiving station (output PGM1), are technical information from the devices. Acceptance of the alarm by the duty officer at the command post is a separate event, logged independently. Loss of communication between the transmitter and the receiving centre itself is signalled on output PGM3, which is the transmitter's own function.
When an alarm arrives, the station switches on the red lamp and the siren, alerting the duty officers to the event
The yellow lamp signals a problem with a flashing pattern in line with EN 60073: AC power loss, battery failure, network failure, display failure, enclosure opened or GSM modem failure
The green lamp is lit during normal operation, confirming that the station is operational
The station continuously checks the status of the AC supply, batteries, cabinet door and display
Automatic detection and recovery of modem failures
Continuous synchronisation with the receiving centre and periodic station status reporting, enabling remote supervision of its operability
The alarm does not end on the station display. At headquarters integrated with SWD-ST, the receiving station creates an incident entry in the State Fire Service command support system (SWD-ST).
The receiving station automatically creates an incident entry in the headquarters' SWD-ST (at headquarters integrated with SWD-ST); once the alarm is accepted, the entry is closed. The entry is created only by the headquarters' receiving station.
Dual-path operation is not limited to transmission from the premises. The retransmission station connects to every receiving station over two independent paths, neither of them connected to the Internet.
| Path | Medium | Role |
|---|---|---|
| Wired | Ethernet IP link in a separate IP MPLS network, isolated from the Internet | Every command sent in parallel with the other path |
| GSM | GSM 4G/LTE, dedicated APN, no Internet access | Every command sent in parallel with the other path |
Commands to the station are sent over both paths in parallel, so command delivery time does not depend on detecting a failure of either path.
The wired path runs in the separate Orange Polska IP MPLS network, with no connection to the Internet, and the GSM path in a dedicated APN; the two are physically separate and independent. Loss of either path is an event visible to the operating staff, because operation without redundancy must not go unnoticed. The details and the effect on the availability figure are described in the section what counts as unavailability.
| Component | Role |
|---|---|
| Industrial controller | Industrial controller with an input/output module: the core of the station, controlling the signalling devices and supervising states (power supply, batteries, cabinet door, display) |
| Visual indicator | LED lamps: green (normal operation), yellow (fault), red (alarm) |
| Audible indicator | Siren or buzzer activated on alarm |
| Display | Touchscreen display, min. 7", with a dedicated FireCom system interface |
| 4G/LTE modem | Second, parallel communication path to the retransmission station (dedicated APN) |
| Power supply | Battery-backed power supply, 30 minutes of backup operation |
| Optional | Remote notification device with a touchscreen at the command post, with a redundant connection |
The station has been designed in line with the requirements of the Regulation of the Polish Minister of the Interior and Administration of 20 June 2007 (Journal of Laws (Dz.U.) 2007 No. 143 item 1002, as amended) and the technical specification CLC/TS 50136-4:2004. The product documentation includes test and inspection procedures after installation. Details in the standards and compliance section.