Standards and compliance of the fire alarm transmission system

EN 54-21, EN 54-4, EN 50136-1-1, CLC/TS 50136-4 and the Polish MSWiA regulation: classification of the transmission system, requirements for transmission paths and how availability is calculated.

Reference standards

The FireCom fire alarm and fault warning transmission system has been designed in line with the requirements of the Regulation of the Polish Minister of the Interior and Administration (MSWiA) and the standards listed below.

Availability classes according to EN 50136-1-1

The standard classifies premises by the minimum monthly availability of the transmission system. The FireCom System monitors availability and calculates it daily.

Availability classes A0 to A4 according to EN 50136-1-1 Chart of minimum monthly availability for five classes. Class A0 sets no requirements. A1 requires 75 per cent monthly and 97 per cent annually. A2 requires 91 and 99.3 per cent. A3 requires 95 and 99.5 per cent. A4, the highest class, requires 98.5 per cent monthly and 99.8 per cent annually. Minimum monthly availability A0 no requirements 0% annual 0% A1 low 75% annual 97% A2 medium 91% annual 99.3% A3 high 95% annual 99.5% A4 highest 98.5% annual 99.8%
The class is assigned to the premises. The system calculates availability daily and compares it with the monthly and annual thresholds of the assigned class.
Availability classes with monthly and annual thresholds
ClassMinimum monthly availabilityAnnual thresholdLevel
A00%0%Basic, no requirements
A175%97%Low
A291%99.3%Medium
A395%99.5%High
A498.5%99.8%Highest

Path loss reporting time classes (T)

The T class defines the maximum time to detect and report the loss of a transmission path, not the alarm transmission time. In the FireCom System, the wired path operates in class T5 (90 s) and the GSM path in class T3 (300 min).

Path loss reporting time classes T1 to T6 according to EN 50136-1-1 Maximum time to detect and report the loss of a transmission path in six classes, shown on a logarithmic scale. T1 is 32 days, T2 is 25 hours, T3 is 5 hours and is the class of the GSM path in the FireCom System, T4 is 3 minutes, T5 is 90 seconds and is the class of the wired path in the FireCom System, T6 is 20 seconds. Maximum time to report path loss T1 periodic reporting 32 days T2 daily reporting 25 hours T3 FireCom GSM path 5 hours T4 fast supervision 3 minutes T5 FireCom wired path 90 seconds T6 fastest supervision 20 seconds
The scale is logarithmic: there are five orders of magnitude between T1 and T6. The FireCom wired path operates in class T5 (90 seconds), the GSM path in class T3 (300 minutes).
Path loss reporting time classes according to EN 50136-1-1
ClassMax. time to report path lossApplication
T132 daysPeriodic reporting
T225 hoursDaily reporting
T35 hours (300 min)Frequent reporting; GSM path in the FireCom System
T43 minutesFast supervision
T590 secondsVery fast supervision; wired path in the FireCom System
T620 secondsFastest supervision

Alarm transmission time (classes D and M)

The transmission time of the alarm itself is described by classes D (transmission time) and M (maximum transmission time). The FireCom System meets classes D4 and M4.

Alarm transmission time in the FireCom System
ClassParameterValue
D4Transmission time, meanunder 10 s
D4Transmission time, 95th percentileunder 15 s
M4Maximum transmission time20 s

For the FireCom System, the full end-to-end transmission time is given: measured from the moment the fire detection and alarm system passes on the alarm signal until the alarm is made available by the notification device of the receiving station at the State Fire Service headquarters.

Overall system classification

EN 50136-1-1 classifies a transmission system using six independent sets of classes. Overall classification of the FireCom System: D4, M4, T5/T3, A4, S2, I2.

Classification of the FireCom System according to EN 50136-1-1
SymbolParameterFireCom classValue
DTransmission timeD4mean under 10 s, 95% under 15 s
MMaximum transmission timeM420 s
TPath loss reporting timeT5 / T3wired path 90 s, GSM path 300 min
AAvailabilityA4at least 98.5% monthly, 99.8% annually
SSubstitution securityS2encryption and authentication with the per-premises encryption key
IInformation securityI2encryption and protection against modification

Transmission paths in the FireCom System

The FireCom System sends every alarm simultaneously and independently over two physically separate, bidirectional transmission paths, in line with the requirements of the MSWiA regulation for fire alarm transmission systems. Both paths qualify as Type 1 links. The retransmission station acknowledges every message to the transmitter with an automatic technical acknowledgement (ACK), and receipt of the alarm is confirmed by the receiving station; this confirmation returns to the control panel at the premises on output PGM1.

How availability is calculated

We calculate availability daily using the EN 50136-1-1 method and report it monthly and annually.

The availability figure includes loss of communication with the premises on all paths, unavailability of the receiving station on both paths, exceeded transmission time and planned maintenance breaks. Loss of a single path, a missing test message and partial faults are logged and signalled, but do not reduce the availability figure.

CLC/TS 50136-4 requirements for the receiving centre

The standard describes how the receiving side should behave: how alarms are queued, how much time the duty officer has to respond and what happens when the limit is exceeded.

The receiving station and the centre meet the requirements of CLC/TS 50136-4 for queuing and prioritisation of alarms, acceptance time limits with escalation, supervision of expected messages, alarm indications and access levels. The queue is ordered by event priority: fire alarms are handled first. An alarm not accepted by the duty officer within the set time and an unacknowledged fault are escalated. The station has four access levels in line with CLC/TS 50136-4, from view-only access without permissions to service with physical access to the device.

Device activity monitoring

A device that does not report within the set time is automatically marked as unavailable. A periodic test schedule is defined for each premises, and a missing expected test message is logged separately, as a diagnostic event.

What counts as unavailability

Under EN 50136-1-1, only the loss of both paths counts as unavailability; the loss of one path is always signalled and logged.

Transmission runs over two independent paths simultaneously, so if one path is lost, the alarm still arrives over the other. The same principle applies to the paths of the alarm transmission equipment and to the communication paths to the receiving station.

Operation without redundancy must not, however, go unnoticed. Loss of one of the receiving station's paths triggers three actions:

  • A fault warning sent to the operator's fault receiving centre, activating visual signalling and requiring acknowledgement like any other fault. The screens at State Fire Service headquarters are not burdened with technical events.
  • A path degradation record in the availability log, for record-keeping and periodic reports.
  • A path indication in the interface, together with the time of the last switchover.

Restoring the path automatically resolves the fault warning, clears the signalling and closes the fault record.

Certification and admission

The FireCom alarm transmission equipment holds certificate of conformity No. 1922-CPR-2083 with EN 54-21:2006 and EN 54-4, issued by notified body No. 1922 "Dedal", and a declaration of performance (DoP) in accordance with Regulation (EU) No 305/2011 (CPR).

The FireCom System, together with the receiving station, is undergoing the approval procedure: we are awaiting the Polish National Technical Assessment (KOT) and the CNBOP-PIB certificate of admission (CNBOP-PIB: Scientific and Research Centre for Fire Protection, National Research Institute, in Józefów, Poland's fire protection approval body). We will confirm the current status of the procedure on request; please contact us.