EN 54-21, EN 54-4, EN 50136-1-1, CLC/TS 50136-4 and the Polish MSWiA regulation: classification of the transmission system, requirements for transmission paths and how availability is calculated.
The FireCom fire alarm and fault warning transmission system has been designed in line with the requirements of the Regulation of the Polish Minister of the Interior and Administration (MSWiA) and the standards listed below.
Fire detection and fire alarm systems. Alarm transmission and fault warning routing equipment. The reference standard for the FireCom alarm transmission equipment installed at the protected premises. The equipment holds certificate of conformity No. 1922-CPR-2083 with EN 54-21:2006 and EN 54-4.
Fire detection and fire alarm systems. Power supply equipment. The standard covering the power supply of the FireCom alarm transmission equipment, including primary and backup power and power supply supervision. Covered by the same certificate, 1922-CPR-2083.
Alarm transmission systems. General requirements for alarm transmission systems. It defines availability classes and reporting time classes, as well as the method of calculating system availability.
Alarm transmission systems. Requirements for equipment used in alarm receiving centres. The reference standard to which the receiving station was designed, covering the message queue, acceptance time limits, escalation and access levels.
Regulation of the Polish Minister of the Interior and Administration of 20 June 2007 on the list of products used to ensure public safety or to protect health, life and property, and on the rules for granting admission of these products for use (Journal of Laws (Dz.U.) 2007 No. 143 item 1002, as amended). It sets out the requirements for fire alarm and fault warning transmission systems. The FireCom System's transmission paths are described in a separate section.
The standard classifies premises by the minimum monthly availability of the transmission system. The FireCom System monitors availability and calculates it daily.
| Class | Minimum monthly availability | Annual threshold | Level |
|---|---|---|---|
| A0 | 0% | 0% | Basic, no requirements |
| A1 | 75% | 97% | Low |
| A2 | 91% | 99.3% | Medium |
| A3 | 95% | 99.5% | High |
| A4 | 98.5% | 99.8% | Highest |
The T class defines the maximum time to detect and report the loss of a transmission path, not the alarm transmission time. In the FireCom System, the wired path operates in class T5 (90 s) and the GSM path in class T3 (300 min).
| Class | Max. time to report path loss | Application |
|---|---|---|
| T1 | 32 days | Periodic reporting |
| T2 | 25 hours | Daily reporting |
| T3 | 5 hours (300 min) | Frequent reporting; GSM path in the FireCom System |
| T4 | 3 minutes | Fast supervision |
| T5 | 90 seconds | Very fast supervision; wired path in the FireCom System |
| T6 | 20 seconds | Fastest supervision |
The transmission time of the alarm itself is described by classes D (transmission time) and M (maximum transmission time). The FireCom System meets classes D4 and M4.
| Class | Parameter | Value |
|---|---|---|
| D4 | Transmission time, mean | under 10 s |
| D4 | Transmission time, 95th percentile | under 15 s |
| M4 | Maximum transmission time | 20 s |
For the FireCom System, the full end-to-end transmission time is given: measured from the moment the fire detection and alarm system passes on the alarm signal until the alarm is made available by the notification device of the receiving station at the State Fire Service headquarters.
EN 50136-1-1 classifies a transmission system using six independent sets of classes. Overall classification of the FireCom System: D4, M4, T5/T3, A4, S2, I2.
| Symbol | Parameter | FireCom class | Value |
|---|---|---|---|
| D | Transmission time | D4 | mean under 10 s, 95% under 15 s |
| M | Maximum transmission time | M4 | 20 s |
| T | Path loss reporting time | T5 / T3 | wired path 90 s, GSM path 300 min |
| A | Availability | A4 | at least 98.5% monthly, 99.8% annually |
| S | Substitution security | S2 | encryption and authentication with the per-premises encryption key |
| I | Information security | I2 | encryption and protection against modification |
The FireCom System sends every alarm simultaneously and independently over two physically separate, bidirectional transmission paths, in line with the requirements of the MSWiA regulation for fire alarm transmission systems. Both paths qualify as Type 1 links. The retransmission station acknowledges every message to the transmitter with an automatic technical acknowledgement (ACK), and receipt of the alarm is confirmed by the receiving station; this confirmation returns to the control panel at the premises on output PGM1.
A dedicated path in the separate Orange Polska IP MPLS network, with no connection to the Internet, secured at the interface with the premises. Encryption with the per-premises encryption key, traffic isolation and continuous supervision of path continuity: loss of the path is detected and reported as a fault. Type 1 link.
A dedicated transmission path set up in the operator's public network, in a dedicated APN, with dedicated SIM cards assigned to the devices, with no Internet access, physically separate from and independent of the wired path. The fire monitoring system operator, Orange Polska, holds a radio licence for use of the path, granted on an exclusive basis. Type 1 link.
We calculate availability daily using the EN 50136-1-1 method and report it monthly and annually.
The availability figure includes loss of communication with the premises on all paths, unavailability of the receiving station on both paths, exceeded transmission time and planned maintenance breaks. Loss of a single path, a missing test message and partial faults are logged and signalled, but do not reduce the availability figure.
The standard describes how the receiving side should behave: how alarms are queued, how much time the duty officer has to respond and what happens when the limit is exceeded.
The receiving station and the centre meet the requirements of CLC/TS 50136-4 for queuing and prioritisation of alarms, acceptance time limits with escalation, supervision of expected messages, alarm indications and access levels. The queue is ordered by event priority: fire alarms are handled first. An alarm not accepted by the duty officer within the set time and an unacknowledged fault are escalated. The station has four access levels in line with CLC/TS 50136-4, from view-only access without permissions to service with physical access to the device.
A device that does not report within the set time is automatically marked as unavailable. A periodic test schedule is defined for each premises, and a missing expected test message is logged separately, as a diagnostic event.
Under EN 50136-1-1, only the loss of both paths counts as unavailability; the loss of one path is always signalled and logged.
Transmission runs over two independent paths simultaneously, so if one path is lost, the alarm still arrives over the other. The same principle applies to the paths of the alarm transmission equipment and to the communication paths to the receiving station.
Operation without redundancy must not, however, go unnoticed. Loss of one of the receiving station's paths triggers three actions:
Restoring the path automatically resolves the fault warning, clears the signalling and closes the fault record.
The FireCom alarm transmission equipment holds certificate of conformity No. 1922-CPR-2083 with EN 54-21:2006 and EN 54-4, issued by notified body No. 1922 "Dedal", and a declaration of performance (DoP) in accordance with Regulation (EU) No 305/2011 (CPR).
The FireCom System, together with the receiving station, is undergoing the approval procedure: we are awaiting the Polish National Technical Assessment (KOT) and the CNBOP-PIB certificate of admission (CNBOP-PIB: Scientific and Research Centre for Fire Protection, National Research Institute, in Józefów, Poland's fire protection approval body). We will confirm the current status of the procedure on request; please contact us.